The Perkins 4006-23TAG2A is a 22.921-litre, six-cylinder diesel engine for generator sets rated up to 750 kVA prime and 825 kVA standby. It belongs to the Perkins 4000 Series, a heavy-duty power-generation platform covering 6-, 8-, 12- and 16-cylinder engine configurations.
A defining feature of this model is that the published generator ratings remain 750 kVA prime and 825 kVA standby at both 1500 rpm and 1800 rpm. The engine power values, frequency configuration and Build List still differ by rated speed, so the 50 Hz and 60 Hz versions must be identified separately before an engine replacement or genset project is approved.
Same Generator Rating, Different Speed Configuration
The 4006-23TAG2A can be supplied for 1500 rpm / 50 Hz and 1800 rpm / 60 Hz generator systems. Both versions are listed at the same generator-output ratings, but their gross and net engine powers are not identical.
| Rated Speed | Duty | Gross Engine Power | Net Engine Power | Generator Output | Electrical Output |
|---|---|---|---|---|---|
| 1500 rpm | Prime | 658 kW (882 hp) | 632 kW (847 hp) | 750 kVA | 600 kWe |
| 1500 rpm | Standby | 721 kW (967 hp) | 695 kW (932 hp) | 825 kVA | 660 kWe |
| 1800 rpm | Prime | 684 kW (917 hp) | 638 kW (855 hp) | 750 kVA | 600 kWe |
| 1800 rpm | Standby | 759 kW (1018 hp) | 702 kW (941 hp) | 825 kVA | 660 kWe |
Why Matching kVA Does Not Make the Versions Interchangeable
The 1500 rpm and 1800 rpm versions require different generator frequencies, engine settings and supporting genset configurations. An existing 50 Hz installation should not be converted to 60 Hz, or vice versa, only because both versions publish the same 750/825 kVA output.
Before approving a replacement, confirm the rated speed, original Build List, complete Engine Serial Number, alternator, control system, radiator arrangement and generator-set manufacturer.
Continuous, Prime and Standby Duty at 1500 rpm
The supplied product information identifies three operating levels for the 1500 rpm / 50 Hz configuration. Each rating describes a different duty and should be matched to the expected annual operating pattern.
| 1500 rpm Duty | Generator Output | Selection Meaning |
|---|---|---|
| Continuous Baseload | 600 kVA | For the approved continuous-load operating profile |
| Prime | 750 kVA / 600 kWe | For the approved variable-load prime-power duty |
| Standby | 825 kVA / 660 kWe | For emergency standby operation within the applicable limits |
A project intended for regular operation should not be sized only from the 825 kVA standby figure. The required duty, expected load profile and operating hours should be defined before the engine and alternator are selected.
Cooling Configuration Is Part of the Engine Specification
The 4006-23TAG2A is listed with temperate and tropical cooling configurations. The supplied information states that the cooling system can be configured for ambient temperatures up to 50°C, but the applicable cooling package must be confirmed against the exact Build List.
| Cooling Decision | Information to Confirm |
|---|---|
| Climate Configuration | Temperate or tropical cooling version |
| Maximum Ambient Temperature | Site design temperature; supplied information states configurations up to 50°C |
| Radiator Arrangement | Radiator model, fan drive, airflow direction and package scope |
| Enclosure Ventilation | Air inlet, hot-air discharge, recirculation risk and pressure restriction |
| Coolant Circuit | Hose routing, expansion arrangement, coolant specification and service access |
| Site Conditions | Altitude, dust, humidity and expected load profile |
A tropical radiator should not be assumed from the engine model name alone. The quotation and nameplate information should identify which cooling configuration is included.
4000 Series Mechanical Platform
With a displacement of 22.921 litres and a dry weight of 2524 kg, the 4006-23TAG2A is a large industrial engine package. Foundation loading, lifting equipment, enclosure dimensions and maintenance access should be reviewed early in the genset design.
| Mechanical Parameter | Specification |
|---|---|
| Cylinder Arrangement | 6 vertical cylinders in line |
| Bore × Stroke | 160 × 190 mm (6.3 × 7.5 in) |
| Displacement | 22.921 L (1397 in³) |
| Aspiration | Turbocharged, air-to-air charge cooled |
| Operating Cycle | 4-stroke |
| Combustion System | Direct injection |
| Compression Ratio | 13.6:1 |
| Rotation Viewed from Flywheel | Anti-clockwise |
| Cooling System | Water-cooled |
| Total Lubricating Capacity | 113.4 L (29.5 US gal) |
| Total Coolant Capacity | 105 L (27.7 US gal) |
| Dimensions (L × W × H) | 3027 × 1706 × 1964 mm (119 × 67 × 77 in) |
| Dry Weight | 2524 kg (5564 lb) |
Cylinder-Head and Fuel-System Design
Each cylinder uses an individual four-valve cylinder head. The separate heads support gas flow and allow cylinder-level service work without treating the complete cylinder bank as one head assembly.
Unit fuel injectors are used for fuel atomisation and controlled combustion. Injector selection, calibration and replacement should be confirmed from the Build List and complete ESN rather than from the 4006-23TAG2A model name alone.
Shared 4000 Series Components
The 4000 Series uses shared component principles across several engine sizes, which can reduce the number of spare-part families required by fleet operators. This does not mean that parts are universally interchangeable between 4006, 4008, 4012 and 4016 engines. Every component must still be matched to the individual engine record.
Build Lists DGBF8527 and DGBF1002
The principal version in the supplied page uses Build Lists DGBF8527 and DGBF1002. DGB8527 and DGB1002 are the updated shortened designations used for engines from later production batches.
| Build List | Identification Note |
|---|---|
| DGBF8527 / DGBF1002 | Original Perkins designations assigned in 2008 |
| DGB8527 / DGB1002 | Updated designations used for later production batches |
The supplied information treats the original and updated designations as the same stated engine specification with identical parts compatibility. The complete ESN is still required because it identifies the production record of the individual engine.
Information to Record from the Nameplate
- Complete engine model: 4006-23TAG2A
- Build List beginning with DGB or DGBF
- Complete Engine Serial Number
- Rated speed: 1500 rpm or 1800 rpm
- Original generator-set manufacturer and model
- Cooling configuration when known
The engine nameplate is normally mounted on the rocker-cover or timing-case area. A clear photograph of the complete plate is recommended because manually copied serial numbers are easily entered incorrectly.
Different 4006-23TAG2A Build Versions
The model name covers several E/U and E/P versions with different speed, regional and emissions designations. The Build List should therefore be treated as part of the product name during quotation and parts identification.
| Version | Build List | 1500 rpm | 1800 rpm | Rating Information in Supplied Page |
|---|---|---|---|---|
| 4006-23TAG2A (E/U) | DGBF8527 / DGBF1002 | Available | Available | 750 / 825 kVA at both speeds |
| 4006-23TAG2A (E/U) | DGBF6434 / DGBF0008 | Available | Not listed | Not provided |
| 4006-23TAG2A (E/U), India | DGBF0011S / DGBF8110S | Available | Not listed | Not provided |
| 4006-23TAG2A (E/P) | DGBF6001 | Available | Not listed | Not provided |
| 4006-23TAG2A (E/P) | DGBF6042 | Not listed | Available | Not provided |
| 4006-23TAG2A (E/P), TA LUFT | DGBF8460 | Available | Not listed | Not provided |
Ratings from one Build List should not be transferred to another version without supporting Perkins documentation. Regional, speed and emissions-specific builds may have different equipment or calibration even when the base model name is the same.
TA Luft Emissions Identification
The supplied content lists gaseous emissions to the 1/2 TA Luft (1986) standard among the model’s design features and separately identifies DGBF8460 as a 1500 rpm TA LUFT version.
Emissions compliance should therefore be quoted against the exact Build List and its supporting documentation. The 4006-23TAG2A model name alone should not be used as proof that every regional version carries the same emissions approval.
Comparing the TAG2A and TAG3A
The Perkins 4006-23TAG3A shares the six-cylinder, 22.921-litre 4006 platform but occupies a different published output position. The applicable rating, Build List, cooling package and application limits should be compared using the official data for each engine.
A TAG3A should not be proposed as a direct TAG2A replacement solely because the dimensions or base architecture appear similar. Alternator matching, coupling, radiator, exhaust, fuel settings and control integration must be reviewed.
Fuel Consumption at 1500 rpm
The supplied fuel-consumption values are stated in litres per hour for the 1500 rpm configuration. They correspond to different duties and load points and should not be compared without considering the delivered output at each point.
| 1500 rpm Operating Point | Approximate Fuel Consumption |
|---|---|
| Standby | 173 L/hr |
| Prime | 157 L/hr |
| Continuous Baseload | 127 L/hr |
| 75% Load | 121 L/hr |
| 50% Load | 83 L/hr |
Actual consumption depends on fuel properties, site conditions, alternator efficiency, engine condition and the load profile of the complete generator set. These values should be used as rating references rather than guaranteed site-consumption figures.
Maintenance Baseline
The stated standard oil-change interval is 500 operating hours under standard conditions. A shorter interval may be required for severe loads, high dust levels, poor fuel quality, prolonged low-load operation or abnormal oil-analysis results.
| Maintenance Item | Planning Requirement |
|---|---|
| Standard Oil-Change Interval | 500 operating hours under standard conditions |
| Lubricating-System Capacity | 113.4 L (29.5 US gal) |
| Cooling-System Capacity | 105 L (27.7 US gal) |
| Oil Specification | Confirm from the Operation and Maintenance Manual for the applicable Build List |
| Severe-Duty Service | Review whether shorter service intervals are required |
| Parts Identification | Use the complete Build List and ESN |
Original Perkins Replacement Parts
The following references are listed as original Perkins components. The supplied page states full parts availability for the DGB/DGBF8527 Build List family. Other versions should be checked separately. Additional Perkins engine parts can be reviewed by component category.
| Item | Part Name | Part Number |
|---|---|---|
| 1 | Intake and Exhaust Valve | SE7AG/14 |
| 2 | Small End Bush | SE91B/7 or Y01/00023 |
| 3 | Valve Guide | T401899 |
| 4 | Valve Spring | 365/472 |
| 5 | Valve Collet | HW7B/18 |
| 6 | Fuel Filter | SE429B/4 or 4759205 |
| 7 | Exhaust Manifold | SE15BZ, SE15BV, SE15BU, SE15BS |
| 8 | Air Filter Assembly | S551A |
| 9 | Connecting Rod Assembly | SE91T |
| 10 | Big End Bearing Kit | SE91AA/3M |
| 11 | Piston and Ring Kit | SE901BA |
| 12 | Piston Ring Kit | 359/552 |
| 13 | Starter Motor | 701/136 |
| 14 | Alternator Belt | 541/398 |
| 15 | Injector | 858/34 |
| 16 | Oil Pump | SE116AE |
| 17 | Oil Filter | 4324909 / SE111B |
| 18 | Water Pump Kit | SE145AX or SE145BK |
Several components have more than one listed reference. Do not select an alternative by appearance or dimensions alone. Build List and ESN verification is required before the final part number and quantity are released.


Parallel Generator Operation
Generator sets using the 4006-23TAG2A can operate in parallel when the complete units have compatible controllers, alternators, voltage regulators, synchronization equipment, protection settings and load-sharing functions.
Parallel capability is a property of the complete generator system, not of the engine model alone. The operating sequence and maximum permitted load steps should be reviewed before commissioning.
Procurement and Export Release
Availability should be confirmed when the inquiry is submitted. The stated lead time is typically 3–4 weeks, while quotations are provided within 24 hours after the engine configuration, quantity and delivery terms have been defined.
| Procurement Item | Supply Information |
|---|---|
| Supply Source | Genuine Perkins through a first-tier authorised distributor channel |
| Quotation Basis | Build List, rated speed, cooling configuration, quantity and delivery terms |
| Quotation Time | Within 24 hours after receiving complete inquiry information |
| Typical Lead Time | 3–4 weeks, subject to availability confirmation |
| Pre-Shipment Verification | ESN and engine nameplate checked before dispatch |
| Engine Test Report | Available on request |
| Export Documents | Commercial invoice, packing list, bill of lading and certificate of origin |
| Shipping | FCL or LCL from Shenzhen, Guangzhou or Shanghai |
| Packaging | Crating and export packaging included |
| Export Experience | Supplied to more than 30 countries |


Warranty and Claim Review
The stated warranty period is 12 months or the manufacturer-specified operating hours from the commissioning date, whichever occurs first.
Conditions Outside Warranty Coverage
- Incorrect installation or improper commissioning
- Failure to follow the applicable Perkins Operation and Maintenance Manual
- Normal consumption of filters, belts, coolant and lubricants
- Damage caused by contaminated fuel or an incorrect lubricant specification
- Cooling-system neglect
- Unauthorised modification or repair during the warranty period
- Transit damage not reported within three working days of delivery
Information Required for Technical Review
- Complete Build List and ESN
- Current operating hours
- Fault description and operating conditions
- Available fault codes
- Photographs of the affected area
- Commissioning and maintenance records relevant to the fault
The stated engineering-review time is within two business days after the required information has been received. Depending on the assessment, the proposed response may include replacement parts, coordinated repair support or an engine exchange.
Transit Damage Procedure
Inspect the shipment before signing the delivery receipt. Photograph visible damage before unpacking, record it on the receipt and notify the supplier within three working days. Do not commission a visibly damaged engine before the transport-damage report has been reviewed.
Perkins 4006-23TAG2A FAQ
Does the engine have the same output at 1500 rpm and 1800 rpm?
The published generator outputs are the same: 750 kVA prime and 825 kVA standby. The gross and net engine powers differ by speed, so the 50 Hz and 60 Hz configurations should still be treated as separate builds.
Which Build Lists apply to the main dual-speed version?
The supplied page identifies DGBF8527 / DGBF1002 and their updated designations DGB8527 / DGB1002. The complete ESN is also required for final confirmation.
Can the engine be supplied for high ambient temperatures?
Temperate and tropical cooling configurations are listed, and the supplied information refers to cooling designs up to 50°C ambient. The exact radiator and cooling version must be confirmed against the Build List.
What is the standard oil-change interval?
The stated standard interval is 500 operating hours under normal conditions. Severe duty or oil-analysis results may require a different interval.
What is the 1500 rpm continuous rating?
The supplied information states 600 kVA continuous baseload, 750 kVA prime and 825 kVA standby at 1500 rpm.
Can several 4006-23TAG2A generator sets operate in parallel?
Yes, when the complete generator sets have compatible synchronization, protection, voltage regulation, controller and load-sharing systems.
Is every 4006-23TAG2A version TA Luft rated?
The source identifies a TA LUFT-specific 1500 rpm Build List, DGBF8460. Emissions status should be confirmed from the exact Build List and supporting documentation rather than from the model name alone.
What information is required for an engine or parts quotation?
Provide the complete model, Build List, ESN, rated speed, cooling configuration, required duty, destination and original generator-set information when replacing an existing engine.
Request a 4006-23TAG2A Configuration Review
Submit the following through the engine inquiry and quotation page:
- Build List beginning with DGB or DGBF
- Complete ESN or a clear photograph of the nameplate
- Required rated speed: 1500 rpm or 1800 rpm
- Required frequency: 50 Hz or 60 Hz
- Continuous, prime or standby duty
- Temperate or tropical cooling requirement
- Maximum site ambient temperature and altitude
- Generator-set manufacturer and model for a replacement project
- Required quantity, delivery terms and destination port
- Required emissions, export and test documentation