Perkins 2206A-E13TAG3 Diesel Engine 400-438KVA |1500/1800rpmОписание продукта
The 2206A-E13TAG3 is a 12.5-litre six-cylinder ElectropaK diesel engine from the Perkins 2200 Series, developed on a proven heavy-duty industrial base and purpose-built for prime and standby power generation in the 400–438 KVA output range. It is suited to data centres, industrial facilities, mining operations, and critical infrastructure projects demanding reliable power across 50 Hz and 60 Hz grids. The TAG3 delivers a meaningful step up in prime power output over the TAG2 while retaining the same 2200 Series platform architecture, with the added capability of field-switchable frequency to reduce inventory complexity for OEMs and distributors serving both 50 Hz and 60 Hz markets.
2206A-E13TAG3 Engine Technical Specifications
| Parameter | Value |
|---|---|
| Configuration | ElectropaK |
| Cylinders | 6, Vertical In-Line |
| Displacement | 12.5 L (762.8 in³) |
| Bore × Stroke | 130 × 157 mm (5.1 × 6.1 in) |
| Aspiration | Turbocharged, aftercooled |
| Combustion | Direct Injection |
| Compression Ratio | 16.3:1 |
| Rotation (from Flywheel) | Anti-Clockwise |
| Lubricating Oil Capacity | 40 L (10.6 US gal) |
| Coolant Capacity | 51 L (13.5 US gal) |
| Exhaust Aftertreatment | None |
| Dimensions (H × L × W) | 1725 × 2410 × 1120 mm (67.9 × 94.9 × 44.1 in) |
| Dry Weight | 1478 kg (3258 lb) |
2206A-E13TAG3 Engine Power Output
| Speed | Rating | Engine Power (Gross) | Engine Power (Net) | Generator Output (kVA) | Generator Output (kWe) |
|---|---|---|---|---|---|
| 1500 rpm | Prime | 368 kW (493 hp) | 349 kW (468 hp) | 400 | 320 |
| 1500 rpm | Standby | 413 kW (554 hp) | 392 kW (526 hp) | 450 | 360 |
| 1800 rpm | Prime | 373 kW (500 hp) | 349 kW (468 hp) | 400 | 320 |
| 1800 rpm | Standby | 407 kW (546 hp) | 381 kW (511 hp) | 438 | 350 |
Build List & Series Compatibility
2206A-E13TAG3 Build List
| Build List | Notes |
|---|---|
| TGDF5013 | Original designation assigned by Perkins (2009) |
| TGD5013 | Updated designation for engines produced in later batches |
Both Build Lists refer to the same engine specification. The difference is production batch only — parts compatibility is identical across both designations.
2206 E13TAG3 Series — Generation Index
| Model | Build List | 1500 rpm (50 Hz) | 1800 rpm (60 Hz) | Prime / Standby (kVA) | Prime / Standby (kVA) |
|---|---|---|---|---|---|
| 2206A-E13TAG3 | TGD / TGDF5013 | ✓ | ✓ | 400 / 450 | 400 / 438 |
| 2206C-E13TAG3 | TGD / TGDF5039 | ✓ | ✓ | 400 / 450 | 400 / 438 |
| 2206C-E13TAG3(E/U) | TGD / TGDF8025 | ✓ | ✓ | —— | —— |
| 2206D-E13TAG3 | TGD / TGDF5082 | — | ✓ | 438 / 500 |
All three generations produce identical power output at the same speed and rating. Generation differences relate to emissions compliance level, not power performance. If your genset frame was built for the 2206A platform, confirm engine mount and flywheel housing dimensions before substituting a C or D generation unit.
Build List Identification Guide
The Build List is stamped on the engine nameplate, mounted on the rocker cover or timing case. Locate the dataplate and read the alphanumeric string beginning with TGD or TGDF.
Nameplate fields to record before ordering:
· Build List (e.g. TGDF5013 or TGD5013)
· Engine Serial Number (ESN)
· Rated speed (1500 or 1800 rpm)
Provide both the Build List and ESN when requesting a quote. This allows us to confirm exact specification match before order commitment.
2206A-E13TAG3 Common Replacement Parts
| Item | Part Name | Part Number | Quality |
|---|---|---|---|
| 1 | Intake Valve | CH12626 | Original Perkins |
| 2 | Exhaust Valve | CH12627 | Original Perkins |
| 3 | Valve Spring Inner | CH12475 | Original Perkins |
| 4 | Valve Spring Outer | CH12754 | Original Perkins |
| 5 | Valve Collet | CH10019 | Original Perkins |
| 6 | Camshaft Bush | CH12630 | Original Perkins |
| 7 | Main Bearing Kit | KRP3120 | Original Perkins |
| 8 | Thrust Washer Kit | KRP3207 | Original Perkins |
| 9 | Connecting Rod Assembly | CH12635 | Original Perkins |
| 10 | Big End Bearing Kit | KRP3023 | Original Perkins |
| 11 | Piston Kit | KRP3024 | Original Perkins |
| 12 | Piston Ring Kit | KRP3025 | Original Perkins |
| 13 | Starter Motor | CH12807 | Original Perkins |
| 14 | Belt | CH12789 | Original Perkins |
| 15 | Fan | CH12009 | Original Perkins |
| 16 | Oil Pump | CH12314 | Original Perkins |
| 17 | Oil Filter Assembly | KRP1719 | Original Perkins |
| 18 | Water Pump | CH12887 | Original Perkins |
Full parts availability for Build List TGD/TGDF5013. Provide ESN for exact part number confirmation.
Procurement & Logistics
· Supply source: Genuine Perkins via first-tier authorised distributor
· Stock status: Confirm availability at inquiry — lead time typically 3–4 weeks
· Export documentation: Commercial invoice, packing list, bill of lading, certificate of origin available as standard
· Shipping: FCL/LCL from Shenzhen/Guangzhou/Shanghai; crating and export packaging included
· Pre-shipment: ESN + nameplate verification completed before dispatch; engine test report available on request




Warranty & After-Sales
Warranty: 12 months or manufacturer-specified hours from date of commissioning, whichever comes first
What the Warranty Does Not Cover
1.Damage resulting from incorrect installation, improper commissioning, or failure to follow the Perkins Operation and Maintenance Manual for TGD/TGDF5013
2.Wear items consumed during normal operation: filters, belts, coolant, lubricants
3.Damage caused by contaminated fuel, incorrect lubricant specification, or coolant system neglect
4.Modifications or repairs carried out by non-authorized personnel during the warranty period
5.Transit damage not reported within 3 working days of delivery — inspect all shipments on receipt and document any damage before signing
Warranty Claim Process
① Document the fault — Record engine serial number, operating hours, fault symptoms, and photographs of the affected area.
② Notify us within warranty period — Submit documentation via email or WhatsApp. Include engine serial number in the subject line.
③ Technical review — Our engineering team reviews the submission within 2 business days and advises on root cause and next steps.
④ Resolution — Depending on fault assessment: replacement parts dispatched, repair support coordinated, or engine exchange arranged. Resolution path confirmed in writing before any action is taken.
After-Sales Support
- Technical enquiries: Email / WhatsApp — 1 business day response
- Parts identification (TGD/TGDF5013): Available on request
- O&M Manual & wiring diagrams: Available on request
- Remote fault diagnosis: Email or video call
Transit Damage Protocol
Photograph damage before unpacking · Note on delivery receipt before signing · Notify us within 3 working days with photos · Do not commission a damaged unit before completing the damage report.
FAQ
Q1: What is the prime power output of the 2206A-E13TAG3?
Net prime power is 349 kW (468 hp) at both 1500 rpm and 1800 rpm. Standby ratings are 392 kW (526 hp) at 1500 rpm and 381 kW (511 hp) at 1800 rpm.
Q2: Does the 2206A-E13TAG3 support both 50 Hz and 60 Hz operation?
Yes. The engine is designed for switchable operation between 50 Hz/1500 rpm and 60 Hz/1800 rpm, allowing a single engine to serve both grid frequency markets.
Q3: What is the Build List for the 2206A-E13TAG3?
The Build List prefix is TGDF. The full Build List reference used in our documentation is TGDF5013. Confirm this prefix on your engine nameplate before ordering parts.
Q4: What does the "A" in 2206A-E13TAG3 mean?
The "A" denotes the Fuel Optimised (unregulated) emissions tier within the 2206-E13TAG3 power segment. "C" indicates Tier 2 and "D" indicates Tier 3. All variants share the same power output and are parts-compatible within the same Build List group.
Q5: What is the difference between the TAG2 and TAG3?
The TAG3 produces 349 kW net prime power versus 313 kW for the TAG2 — an increase of approximately 11%. The TAG3 also supports 1800 rpm/60 Hz operation. Both share the same 2200 Series 6-cylinder 12.5L platform.
Q6: What is the fuel consumption of the 2206A-E13TAG3 at various load levels?
At 1500 rpm prime, fuel consumption at 100% load is 197 g/kWh, reducing to 199 g/kWh at 75% and 202 g/kWh at 50%. At 1800 rpm prime, figures are 196 g/kWh (100%), 199 g/kWh (75%), and 205 g/kWh (50%). Note that fuel consumption data is engine-rated and actual genset consumption will vary with installation and ambient conditions.
Q7: What is the dry weight of the 2206A-E13TAG3 ElectropaK?
Dry weight is 1478 kg (3258 lb). Overall dimensions are 1725 × 2410 × 1120 mm (H × L × W).
Q8: Is this engine available with emissions-compliant variants for regulated markets?
Yes. The 2206C-E13TAG3 (Tier 2) and 2206D-E13TAG3 (Tier 3) are available for markets with emissions requirements. Contact us with your destination country and application for variant selection guidance.
Request a Quote
Provide the following for fastest response:
· Build List (TGD5013 or TGDF5013)
· Engine Serial Number (if replacing existing unit)
· Required rated speed: 1500 rpm / 1800 rpm
· Destination port and required documentation
Perkins 2206A-E13TAG3 Diesel Engine 400-438KVA |1500/1800rpm Сопутствующие товары
-
Perkins 2206C-E13TAG3 6-Cylinder Turbocharged Aftercooled Diesel Engine400 kVA Prime / 450 kVA Standby @ 1500 rpm · 400 kVA Prime / 438 kVA Standby @ 1800 rpm Build List· TGD/TGDF… -
Perkins 2206D-E13TAG3 6-Cylinder Turbocharged Aftercooled Diesel Engine 1800rpmPrime 350kWe / Standby 400kWe · ElectropaK Configuration · Build List TGDF5082